Master Deck Philly Summit .pdf

Master Deck Philly Summit .pdf

Master Deck Philly Summit .pdf

Seeq Summit Philadelphia

OCTOBER 14, 2026

2

HOUSEKEEPING

3

GOVERNANCE

4

Favourite colour Beige

Catchphrase “Can you prove it?”

Hobbies Reading audit trails. For fun.

Last smiled Not documented

Sense of humour

Meet your auditor.

5

Data Integrity

Access Control and Change Management

Readable Audit Trail

Regulatory Documentation

6

AGENDA

7

Johnathan Tan Syringe Process Manager

CUSTOMER STORY: SANOFI

Seeq Summit Presentation

Jonathan Tan

The views and opinions expressed by the speaker are their own and should not be attributed to their employer.

Use cases for Seeq at

Sanofi

Scenario 1. Laminar Flow Monitoring

Process: A machine within the production process manages sterile commodities under controlled laminar airflow to preserve aseptic integrity.

Scenario 1. Laminar Flow Monitoring

Problem: During a filling run, the machine lost power temporarily and therefore lost laminar flow. Time was lost performing remediation cleanings

Scenario 1. Laminar Flow Monitoring

Seeq Resolution: Sensors monitoring laminar flow differential pressure and air speed outputting those signals into process historian, which allowed real time and retrospective data to support remediation decision making.

Scenario 1. Laminar Flow Monitoring

Sanofi Benefit: 1. Decisive remediation based on data 2. Quicker response to troubleshoot issues, leading to less downtime and remediation work

Scenario 2. Filter pressure forecasting

Process: Tank dispenses product into dosing vessel and filters are used sterilize the buffer and product. Problem: Protein clogs the filter, leading to pressure build up on inlet filter and potency concerns in product

Scenario 2. Filter pressure forecasting

Resolution: Seeq screen was built to monitor and anticipate upcoming pressure issues with production.

Scenario 2. Filter pressure forecasting

Sanofi Benefit 1.Visibility and information to make scheduling

decisions based on anticipated production obstacles

2.Guidance on reacting to tank pressure alarms and quick resolution of alarms

Questions?

Ask your process data a question A live demo of the Seeq MCP server, on synthetic data

Philip Brown

Synthetic demo data. Not real process data.

At a glance: a stuck valve found and flagged in six questions

Found FERM-02 is running hot: 38.71 °C now, peak 39.65 °C, while FERM-01 and FERM-03 hold 37 °C

Root cause Its cooling valve is stuck at about 45% while the controller demands 100%

Caught early A live valve-deviation condition flags it on Sep 6, 04:00, 2.3 days before a 38 °C alarm would

Acted on Early warning written to Seeq, work order drafted, one-page summary produced

6 plain-English questions

15 Seeq tool calls: 13 reads, 2 writes

2.3 days earlier warning than a 38 °C alarm

20

Synthetic demo data. Not real process data.

What is MCP?

Claude Understands your question and picks the tools

Seeq MCP server The adapter: turns Seeq's API into 42 named tools

Seeq Your process data: signals, conditions and workbooks

tool call

result

API request

data

A few of the tools your server exposes:

seeq_search_by_name seeq_get_signal_statistics seeq_get_condition_capsules seeq_api (create items)

MCP (Model Context Protocol) is an open standard for connecting AI assistants to tools and data. Think of it as a universal adapter: build the server once, and any MCP-capable assistant can use your system through its named tools.

21

Synthetic demo data. Not real process data.

How it works

You ask

A plain-English question about your process

Claude plans

Chooses which Seeq tools to call and in what order

Seeq answers

The MCP server searches items, reads samples and conditions, and writes results back

Claude only uses the tools your Seeq account allows. Writes go to a workbook you choose.

22

Synthetic demo data. Not real process data.

Guardrails: what Claude can and can't do

Your permissions only

Claude acts as the signed-in Seeq user. It can't see or change anything that account can't.

Writes stay in one place

Everything in this demo was created inside one clearly labelled workbook.

A person stays in the loop

Tool calls can require approval, and the work order stays a draft until someone sends it.

Changes can be undone

Seeq archives items rather than deleting them, so they can be restored.

23

Synthetic demo data. Not real process data.

The scenario: three fermenters, one hidden fault

• Acme Biologics (fictional), Fermentation area

• FERM-01 and FERM-03 run normally at 37 °C

• FERM-02 has a fault we are not told about

• Data window: Sep 1 to Sep 11, 2026, every 4 hours

• All of it lives in one clearly labelled demo workbook

3 fermenters

10 signals

2 conditions

63 samples per signal

24

Synthetic demo data. Not real process data.

The demo: six questions in plain English

1 Connect to the workbook and tell me what's in it Connection, 2 worksheets, 11 items

2 Compare temperature across the three fermenters. Anything off? FERM-02: wider spread, higher peak

3 When did FERM-02 start drifting, and how bad did it get? Sep 6, 16:00. Peak 39.65 °C

4 Why? Check the cooling valve command and position Command 100%, position stuck at 45%

5 Create a live early warning for valve deviation above 5 points, and draft a work order

New formula condition fires Sep 6, 04:00

6 Show me a one-page summary Dashboard with KPIs, timeline, charts

25

Synthetic demo data. Not real process data.

Step 1 of 6: Find the data

You ask

“Connect to the workbook and tell me what's in it”

Behind the scenes

1 Seeq tool call, read-only

1 seeq_connect_workbook

Find the workbook by name, then list every worksheet and the items on it

No IDs needed: Claude finds the workbook by name, and the result hands it the item IDs it uses in steps 2 to 5.

The answer

• Found “ZZ DEMO - Synthetic Fermentation” in My Folder

• Overview worksheet: temperature for all three fermenters, FERM-02 dissolved oxygen, and the High Temp Excursion condition

• Root cause worksheet: cooling valve command and position for all three fermenters

• 2 worksheets, 11 items. Data from Sep 1 to 11, 2026, every 4 hours

Seeq's own view on the next slide →

26

Synthetic demo data. Not real process data.

In Seeq: the Overview worksheet

The workbook Claude found in step 1, in Seeq itself. Top: temperature for all three fermenters, with FERM-02 (red) pulling away from Sep 6. Middle: FERM-02 dissolved oxygen. Bottom: the High Temp Excursion periods (orange).

Seeq shows US Eastern time (UTC−4). The rest of this deck uses UTC, so Sep 6 04:00 UTC appears in Seeq as Sep 6 12:00 AM.

27

Synthetic demo data. Not real process data.

Step 2 of 6: Spot the outlier

You ask

“Compare temperature across the three fermenters. Anything off?”

Behind the scenes

3 Seeq tool calls, read-only

1 seeq_get_signal_statistics

FERM-01 temperature, Sep 1 to 11: 63 samples, avg 36.99 °C, peak 37.25 °C

2 seeq_get_signal_statistics

FERM-02 temperature: avg 37.51 °C, peak 39.65 °C, latest 38.71 °C

3 seeq_get_signal_statistics

FERM-03 temperature: avg 37.01 °C, peak 37.27 °C

The answer

• Yes: FERM-02 is off

• On average it is only 0.5 °C above the others, which is easy to dismiss

• Its peak, 39.65 °C, is 2.4 °C higher than theirs

• It is still at 38.71 °C, 1.7 °C over the 37 °C setpoint

Evidence on the next slide →

28

Synthetic demo data. Not real process data.

The averages hide it. The peaks don't

37.0 37.5 37.0

0

10

20

30

40

FERM-01 FERM-02 FERM-03

Average temperature (°C)

+0.25

+2.65

+0.27

0.0

0.5

1.0

1.5

2.0

2.5

3.0

FERM-01 FERM-02 FERM-03

Peak above the 37 °C setpoint (°C)

+0.5 °C FERM-02 average vs the others

39.65 °C FERM-02 peak, on Sep 10

5.6x more variable than the others (std dev)

29

Synthetic demo data. Not real process data.

Step 3 of 6: Pin down when it started

You ask

“When did FERM-02 start drifting, and how bad did it get?”

Behind the scenes

2 Seeq tool calls, read-only

1 seeq_get_signal_samples

FERM-02 temperature, every reading from Sep 1 to 11: 63 samples

2 seeq_get_condition_capsules

High Temp Excursion (>38 °C): 2 periods, from Sep 8 12:00 and Sep 9 00:00

A condition marks the periods of time when something is true. Each period is called a capsule.

The answer

• Drift began Sep 6, 16:00 at 37.44 °C, above every earlier reading

• It climbed about 0.3 °C per day

• Above 38 °C continuously since Sep 9. Peak 39.65 °C on Sep 10

• A standard 38 °C alarm would not have fired until Sep 8

Evidence on the next slide →

30

Synthetic demo data. Not real process data.

FERM-02 left its band on Sep 6 and kept climbing

36.5

37.0

37.5

38.0

38.5

39.0

39.5

40.0

Sep 1 Sep 2 Sep 3 Sep 4 Sep 5 Sep 6 Sep 7 Sep 8 Sep 9 Sep 10 Sep 11

T e

m p e

ra tu

re ( °C

)

FERM-01 FERM-02 FERM-03 38 °C limit

37.44 °C first out of band, Sep 6 16:00

39.65 °C peak, Sep 10 00:00

38.71 °C latest, Sep 11 08:00

31

Synthetic demo data. Not real process data.

Step 4 of 6: Find the cause

You ask

“Why? Check the cooling valve command and position”

Behind the scenes

6 Seeq tool calls, read-only

1 seeq_get_signal_statistics × 2

FERM-02 valve, Sep 6–11: command 46% → 100%, position 44.2–46.4%

2 seeq_get_signal_statistics × 2

FERM-01 valve: command avg 45.1%, position avg 45.0%

3 seeq_get_signal_statistics × 2

FERM-03 valve: command avg 45.2%, position avg 45.2%

Command is what the controller asks the valve to do. Position is what the valve actually does.

The answer

• FERM-02's cooling valve is stuck

• The controller asked for 100% cooling; the valve stayed at about 45%

• FERM-01 and FERM-03 valves follow their commands, so the cooling supply is fine

• A FERM-02 hardware fault: maintenance must test the valve, actuator and positioner

Evidence on the next two slides →

32

Synthetic demo data. Not real process data.

The valve is stuck: asked for 100%, stuck at 45%

30

40

50

60

70

80

90

100

Sep 1 Sep 2 Sep 3 Sep 4 Sep 5 Sep 6 Sep 7 Sep 8 Sep 9 Sep 10 Sep 11

V a

lv e (

% )

FERM-02 valve command FERM-02 valve position FERM-01 valve position (healthy)

100% command, held since Sep 10

45% position, stuck at 44-46% since Sep 6

Normal FERM-01 and FERM-03 valves follow their commands

33

Synthetic demo data. Not real process data.

In Seeq: the Root cause worksheet

Lane 2 is the root cause: FERM-02 valve command (blue) climbs to 100% while its position (orange) stays flat. Lanes 3 and 4 are FERM-01 and FERM-03, where command and position move together. Seeq shows US Eastern time (UTC−4). The rest of this deck uses UTC, so Sep 6 04:00 UTC appears in Seeq as Sep 6 12:00 AM.

34

Synthetic demo data. Not real process data.

Step 5 of 6: Act on it

You ask

“Create a live early warning for valve deviation above 5 points, and draft a work order”

Behind the scenes

3 Seeq tool calls, 2 writes, both inside the demo workbook

1 seeq_api: POST /conditions

New formula condition: (command − position) > 5, in the demo workbook

2 seeq_add_conditions_to_worksheet_trend

Show the new condition on the Root cause worksheet

3 seeq_get_condition_capsules

Read it back: 1 period, Sep 6 04:00 to Sep 11 08:00

The work order is written in the chat. Nothing is sent outside Seeq.

The answer

• Created “DEMO FERM-02 Valve Deviation (live)”

• It fires Sep 6, 04:00: 2.3 days before the first reading above 38 °C

• It is a formula, so it updates itself as new data arrives

• Draft work order: stroke-test the FERM-02 valve and actuator, check coolant flow

Evidence, Seeq view and work order on the next four slides →

35

Synthetic demo data. Not real process data.

An alert on the valve fires 2.3 days earlier

2.3 days sooner than waiting for a 38 °C alarm

Sep 6, 04:00 Valve deviation above 5 points.

Early warning fires

Sep 6, 16:00 Temperature leaves its normal

band (37.44 °C)

Sep 8, 12:00 First excursion above 38 °C. A

standard alarm fires here

Sep 10, 00:00 Peak 39.65 °C. Valve command

pinned at 100%

2.3 days of warning

Color shows severity: green = caught early, amber to red = escalating impact

36

Synthetic demo data. Not real process data.

In Seeq: the early warning Claude created

After step 5, the new blue Valve Deviation (live) lane at the bottom starts on Sep 6, well before the red High Temp Excursion bars above it. The gap between them is the 2.3 days of warning.

The formula Claude wrote, open in Seeq's formula editor: $cmd and $pos are the FERM-02 valve command and position.

Seeq shows US Eastern time (UTC−4). The rest of this deck uses UTC, so Sep 6 04:00 UTC appears in Seeq as Sep 6 12:00 AM.

37

Synthetic demo data. Not real process data.

From insight to action

Live early warning

A Seeq formula condition, valve command minus position above 5 points. It recalculates as new data arrives.

Written to Seeq

Draft work order

Inspect and stroke-test the FERM-02 cooling valve, with the Seeq evidence attached. Draft only, nothing sent.

Drafted

One-page summary

KPIs, timeline, temperature and valve charts in a single page you can print or share.

dashboard.html

38

Synthetic demo data. Not real process data.

The draft work order

Work order: FERM-02 cooling valve DRAFT · not submitted

Asset FERM-02, Cooling Valve, Acme Biologics >> Fermentation

Priority High. FERM-02 above 37.5 °C since Sep 8, 00:00 (80 hours) and above 38 °C since Sep 9

Raised by Philip Brown, via Claude and Seeq MCP

Detected Sep 6, 04:00 (live valve deviation early warning)

Problem FERM-02 temperature has drifted from 37.0 °C to 38.7 °C (latest reading), with a peak of 39.65 °C. The cooling valve command has risen to 100%, but valve position has stayed at about 45% (range 44.2 to 46.4%) since Sep 6. FERM-01 and FERM-03 valves track their commands within about 1 point.

Requested work 1. Inspect and stroke-test the FERM-02 cooling valve, actuator and

positioner (the data shows the valve is not moving, but cannot yet say which part has failed).

2. Confirm coolant supply and jacket flow are normal. 3. Repair or replace, then confirm position follows command across

the full range.

Follow-ups • Quality to assess batch impact (80 hours above 37.5 °C,

dissolved oxygen depressed).

• Roll the valve-deviation alert out to all fermenters. • Evidence: Root cause worksheet in the ZZ DEMO workbook, with

the Valve Deviation (live) and High Temp Excursion conditions.

39

Synthetic demo data. Not real process data.

Step 6 of 6: Summarize it

You ask

“Show me a one-page summary”

Behind the scenes

No new Seeq calls

1 (no tool calls)

Claude reuses what steps 1 to 5 returned, so nothing new is read from Seeq

The answer

• Now: 38.71 °C, 1.7 °C over setpoint, peak 39.65 °C

• Cause: valve command 100%, position stuck at 44 to 46%

• Caught: Sep 6, 04:00 by the live early warning

• Impact: 80 hours above 37.5 °C; dissolved oxygen down from about 34% to 30%

• Next: repair the valve; quality reviews the batch

The dashboard is on the next slide →

40

Synthetic demo data. Not real process data.

The one-page summary

Left: the whole page. Right: its top section, enlarged. Below that, the page continues with the timeline, the temperature and valve charts, what the data says, and the actions taken.

Interactive version: dashboard.html. It works offline.

41

Synthetic demo data. Not real process data.

From question to action in minutes

Questions, not clicks

Ask in plain English. No hunting through workbenches.

Evidence, not guesses

Root cause found in the data: a stuck valve, not a hunch.

Action, not just insight

A live early warning and a work order, ready to go.

Next steps: wire the condition to notifications, roll the valve-deviation alert out to every fermenter, and try it on your own data.

42

Thank you Questions and discussion

Philip Brown

All data shown is synthetic. Demo workbook: “ZZ DEMO - Synthetic Fermentation”.

44

Kelly Van Dyke Senior Product Manager

Product Roadmap

45

Seeq delivers measurable industrial outcomes because it is

where manufacturing decisions get made.

Seeq is the operational decision layer for Industrial AI

46

Market Research: How do manufacturers make operational decisions?

 Dozens of interviews with senior industry leaders, understanding their decision flows.

 Not Seeq-centric; persona- and decision-centric.

 Outcome-based view focused on complex end-to-end outcomes.

Trigger Exception or target gap.

1 Connect & Codify

Signals, events, context,

documents.

2 Identify Formulas,

models, root-cause, AI

synthesis.

3 Prioritize

Interventions, trade-offs,

impact.

4 Investigate

& decide Accountable

owner records

rationale.

5 Act

Work order, plan change,

agent action. 6

Capture & Quantify Outcome

Measure, compare, update logic,

retain knowledge.

Typical decision flow, mapped to Seeq’s Decision Capital flywheel

Source: interviews conducted by Insight Partners, and Buried Wins

47

Seeq Drives Seeq Supports

Downtime & reliability risk

Production, yield & quality

Energy, emissions & resources

Supply-chain response & planning

Enterprise portfolio & capital allocation

Regulatory & batch release

Seeq as the operational decision layer

Seeq as a key supporting layer

Connect & Codify

Identify Prioritize Investigate & Decide

Act Capture & Quantify

Outcomes What evidence,

context, relationships, and knowledge define

the situation?

What has changed, deviated, or

emerged that may require attention?

Which issues matter most, based

on urgency, impact, and confidence?

What explains the issue, what options

exist, and which response is

appropriate?

How is the selected response

authorized, coordinated, and

executed?

What happened, what value was

realized, and what should inform

future decisions? High-value Decision Categories

Customer Outcomes: How Seeq powers operational decisions

48

Decision Capital is the accumulated institutional intelligence behind better operational decisions: trusted

data, stored calculations, analytics, operating context, expert judgment, decision rationale, actions taken, and

outcomes achieved.

49

Decision Capital creates the record of how an organization actually decides and what happened after – the vital

context needed to create trusted, repeatable, and traceable AI to solve high value problems in complex operating

environments.

50

Decision Capital

Identify & Prioritize

Opportunities

Connect & Codify

Capture & Quantify

Outcome

Investigate,

Decide & Act

51

Amplify Human Intelligence

• Put proactive, SME-guided agents to work throughout the decision loop

• Close the decision → action loop through collaborative, AI-assisted cases that capture the evidence & the “Why”

• Carry decisions into operational workflows across the IT/OT ecosystem (CMMS, EMS, chat, mobile, etc)

Build Scaling Engines

• Deploy proven monitoring across assets, sites & fleets with less effort

• Treat batch & process data as first-class, from definition to repeatable & scalable analysis

• Keep data access & calculations fast, reliable and efficient at enterprise-wide scale

Cultivate Operational Knowledge

• Capture decision context, rationale & outcomes as a by-product of the work

• Infuse data & context enrichment into the platform, to invisibly power users and agents alike

• Reuse accumulated knowledge to make every decision faster, confident, and traceable

Decision Capital

Seeq Product Themes

52

SAFE HARBOR STATEMENT

What follows includes descriptions of unreleased software intended to illustrate planned product direction.

Functionality, priorities, timing, and release plans are subject to change;

some items described may never be released.

53Build Scaling Engines Amplify Human IntelligenceCultivate Operational Knowledge

Proactive, personalized, autonomous AI Chiefs of Staff

Bring enriched data & context into Seeq from anywhere

Power on-the-loop orchestration of AI agents with a Seeq harness

Trigger actions at the point of deciding, with built-in feedback

Scale analytics, dashboards & agents with E2E blueprints

Simplify Seeq administration with flexible governance controls

Make it easy to define, analyze & understand batch process data

Enjoy Seeq from any device with a new responsive Design System

FUTURE

Contextualize data with AI- powered application builder

Go from investigation, to decide & act, with Seeq Cases

Unlock agentic ecosystem inter- op with MCP & Agent Skills

Monitor live signals for variance with operationalized SPC

Make in-context observations easy to capture & reuse

Improve governance with full lifecycle support on Templates

Enforce approval workflows with versioning of work products

NEXT

Seeq Roadmap Highlights

Automate workflows with SME- authored Custom Agents

Conversational dashboard creation & insights

Reduce time to detect variations with SPC charts & run rules

Train & run models with Seeq data via external ML integrations

Organize & codify tag relationships with Tree Builder

Enable scaling to 1000s of monitored conditions with ease

NOW

Legend:

FROM A SIGNAL TO A DECISION

PHILLY SUMMIT PRODUCT TALK

Purification batch investigation

4

THE STORY

One signal. One question. A path to action. Follow the investigation as it moves from signal to operational response.

PURIFICATION

BATCH variable flow

1

SPOT

SPC + operationalize SPC

2

SCALE

Templates + Tree Builder + Scaling Tables

3

DECIDE

Approval workflows + Vantage

4

ACT

Agent Q + Agent Builder

56

SPC

FEATURE VIDEO: OPERATIONALIZE SPC

Turn the analysis into a repeatable monitor

Repeat

Apply the same statistical logic

across batches

Detect

Find the next meaningful shift

Alert

Move from one investigation to

ongoing awareness

4

58

Operationalize

FEATURE VIDEO: TEMPLATES

Package the purification playbook

Capture

Save the analysis once

Reuse

Apply the logic and outputs

again

Govern

Give every investigation a

trusted starting point

5

FEATURE VIDEO: TREE BUILDER

Give the data structure and context

Organize

Connect batches, units,

process steps, and variables

Discover

Make relationships easier to

find

Contextualize

Turn raw tags into a usable

structure

6

FEATURE VIDEO: SCALING TABLES

Apply the playbook across the batch population

Map

Connect the Template to

structured data

Scale

Generate the analysis across

many batches

Adapt

Handle real-world differences

without rebuilding

7

FEATURE VIDEO: APPROVAL WORKFLOWS

Move from finding to reviewing

Route

Send findings to the right

reviewer

Review

Make approval gates explicit

Trace

Keep the decision history

visible

8

67

Approvals

FEATURE VIDEO: VANTAGE

Put the investigation into operational context

Prioritize

Focus on the events that need

attention

Contextualize

Bring data, history, and

expertise together

Learn

Capture what the team learned

for next time

9

FEATURE VIDEO: AGENT BUILDER

Make the investigation repeatable

Encode

Capture the expert workflow

Run

Repeat it when conditions

recur

Scale

Turn a proven approach into a

capability

11

72 72

One investigation becomes an operational capability

• Discover → package → structure → scale

• Review → monitor → reason → automate

• Every batch starts with the best available context

CONNECT ANALYSIS TO ACTION

12

74

Sneak Peaks

75

77

79

81

83

Questions?

84

Break! See you back here at 12:45pm

85

BILL VASILIADIS

Sr. Industry Development Manager

Seeq

SHYAM MUDIRAJ, Ph.D.

Associate Director, Data Science & Analytics

GSK

PHILIP BROWN

Deputy Director - Process Monitoring Data Engineer

Sanofi

ANTHONY QUACH

AI Applications Engineer

Seeq

Panel Discussion: AI, Adoption, and the Art of the Possible

KRISTOPHER MCQUAY

Process Analytics Engineer

The Chemours Company

86

WIFI

Username: Currents Ballroom ub Password: sharks and rays welcome 2 surf

For the workshop: Please login at https://preview.seeq.dev using your email address as your username & password, then click Shared (on the left) ->

https://preview.seeq.dev

87

AI Hands-on- Workshop

88

Closing

89

90

Happy hour! 2:30-4:00pm

Slide 1: Seeq Summit Philadelphia Slide 2: HOUSEKEEPING Slide 3 Slide 4: Meet your auditor. Slide 5 Slide 6: AGENDA Slide 7: CUSTOMER STORY: SANOFI  Slide 8: Seeq Summit Presentation Slide 9: The views and opinions expressed by the speaker are their own and should not be attributed to their employer. Slide 10: Use cases for Seeq at Sanofi Slide 11: Scenario 1. Laminar Flow Monitoring Slide 12: Scenario 1. Laminar Flow Monitoring Slide 13: Scenario 1. Laminar Flow Monitoring Slide 14: Scenario 1. Laminar Flow Monitoring Slide 15: Scenario 2. Filter pressure forecasting Slide 16: Scenario 2. Filter pressure forecasting Slide 17: Scenario 2. Filter pressure forecasting Slide 18: Questions? Slide 19: Ask your process data a question Slide 20: At a glance: a stuck valve found and flagged in six questions Slide 21: What is MCP? Slide 22: How it works Slide 23: Guardrails: what Claude can and can't do Slide 24: The scenario: three fermenters, one hidden fault Slide 25: The demo: six questions in plain English Slide 26: Step 1 of 6: Find the data Slide 27: In Seeq: the Overview worksheet Slide 28: Step 2 of 6: Spot the outlier Slide 29: The averages hide it. The peaks don't Slide 30: Step 3 of 6: Pin down when it started Slide 31: FERM-02 left its band on Sep 6 and kept climbing Slide 32: Step 4 of 6: Find the cause Slide 33: The valve is stuck: asked for 100%, stuck at 45% Slide 34: In Seeq: the Root cause worksheet Slide 35: Step 5 of 6: Act on it Slide 36: An alert on the valve fires 2.3 days earlier Slide 37: In Seeq: the early warning Claude created Slide 38: From insight to action Slide 39: The draft work order Slide 40: Step 6 of 6: Summarize it Slide 41: The one-page summary Slide 42: From question to action in minutes Slide 43: Thank you Slide 44: Product Roadmap Slide 45 Slide 46 Slide 47 Slide 48 Slide 49 Slide 50 Slide 51 Slide 52 Slide 53 Slide 54: FROM A SIGNAL TO A DECISION Slide 55 Slide 56: SPC Slide 57 Slide 58: Operationalize Slide 59 Slide 60 Slide 61 Slide 62 Slide 63 Slide 64 Slide 65 Slide 66 Slide 67: Approvals Slide 68 Slide 69 Slide 70 Slide 71 Slide 72 Slide 73 Slide 74: Sneak Peaks Slide 75 Slide 77 Slide 79 Slide 81 Slide 83: Questions? Slide 84: Break! See you back here at 12:45pm Slide 85 Slide 86: WIFI Username: Currents Ballroom ub Password: sharks and rays welcome 2 surf For the workshop: Please login at https://preview.seeq.dev using your email address as your username & password, then click Shared (on the left) ->   Slide 87: AI Hands-on-Workshop Slide 88: Closing Slide 89 Slide 90: Happy hour! 2:30-4:00pm Slide 91


Item Type: pdf